Tente buscar por palavras-chaves, código de pedido ou produto ou número de série, por exemplo, "CM442" ou "informações técnicas"
Insira pelo menos 2 caracteres para iniciar a busca.
  • Histórico
Prosonic FMU42 - Ultrasonic measurement

Ultrasonic measurement
Time-of-Flight
Prosonic FMU42

Cost effective device for sophisticated level measurement in liquids and bulk solids for up to 10m

FMU42
Please Wait (spinning wheel)
Carregando preços
Preço temporariamente indisponíveis
Price on request
from CHF ??.-
  • Measuring principle

    Ultrasonic

  • Characteristic / Application

    Compact ultrasonic transmitter

  • Supply / Communication

    2/4-wire (HART), PROFIBUS PA, FOUNDATION Fieldbus

  • Accuracy

    +/- 4 mm or +/- 0,2 % of set measuring range

  • Ambient temperature

    -40 °C ... 80 °C
    (-40 °F ... 176 °F)

  • Process temperature

    -40 °C ... 80 °C
    (-40 °F ... 176 °F)

  • Process pressure absolute / max. overpressure limit

    0.7 bar ... 2.5 bar abs
    (10 psi ... 36 psi)

  • Main wetted parts

    PVDF

  • Process connection

    Flange
    DN80, ASME 3", JIS 10K 80
    DN100,ASME 4", JIS 10K 100
    Mounting bracket

  • Blocking distance

    0.4 m (1.3 ft)

  • Tamanho do tanque / aplicação

    Tamanho do tanque / aplicação

  • Max. measurement distance

    Max. measurement distance

  • Communication

    4 ... 20 mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX, FM, CSA, INMETRO, NEPSI

  • Application limits

    Application limits

  • Measuring principle

    Ultrasonic

  • Characteristic / Application

    Compact ultrasonic transmitter

  • Supply / Communication

    2/4-wire (HART), PROFIBUS PA, FOUNDATION Fieldbus

  • Accuracy

    +/- 4 mm or +/- 0,2 % of set measuring range

  • Ambient temperature

    -40 °C ... 80 °C
    (-40 °F ... 176 °F)

  • Process temperature

    -40 °C ... 80 °C
    (-40 °F ... 176 °F)

  • Process pressure absolute / max. overpressure limit

    0.7 bar ... 2.5 bar abs
    (10 psi ... 36 psi)

  • Main wetted parts

    PVDF

  • Process connection

    Flange
    DN80, ASME 3", JIS 10K 80
    DN100,ASME 4", JIS 10K 100
    Mounting bracket

  • Blocking distance

    0.4 m (1.3 ft)

  • Max. measurement distance

    5 m (16 ft)

  • Communication

    4 ... 20 mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX, FM, CSA, INMETRO, NEPSI

  • Application limits

    Take notice of range diagram

Configurar para baixar os desenhos CAD deste produto